Permit: T07CM00837

Parcel: 30503004B

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T07CM00837

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
12/05/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
11/06/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
TALKED WITH UL REGARDING PLUG & CORD CONNECTION OF AUTOMATIC DOOR OPENERS. PART OF THE LISTING REQUIREMENT IS THE INSTRUCTIONS TO SPECIFY CORD & PLUG CONNECTION & TO PROVIDE SPECIFIC INFORMATION ON CORD REQUIREMENTS. PEASE PROVIDE E-FILE NUMBER SO I CAN VERIFY WITH UL IF THESE DOOR OPENERS ARE LISTED TO BE CORD & PLUG CONNECTED.
10/09/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
COMPLETE ALL ITEMS FROM PREVIOUS INSPECTION
ON 9/24/07 APPLIANCES INTENDED OR IDENTIFIED FOR FLEXIBLE CORD CONNECTION EITHER COME WITH CORD INSTALLED AT FACTORY OR HAVE IT WRITTEN IN INSTALLATION INSTRUCTIONS. PLAN ALSO CALLS FOR MOTOR RATED SWITCH NOT RECEPTACLE FOR CONNECTION OF DOOR OPENER.
09/24/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. BATHROOM RECEPTACLES TO BE GFI PROTECTED THIS INCLUDES RECEPTACLE IN LIGHT FIXTURE. NEC 210.8 (B)
2. PROVIDE INSTALLATION INSTRUCTIONS FOR AUTOMATIC DOOR OPENER - BELIEVE IT CANNOT BE CORD & PLUG CONNECTED - NEC 400.7 & 400.8
3. INSTALL EXHAUST FAN COVER
4. COULD NOT FIND APPROVED PLANS