Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/19/2007 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 07/18/2007 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* - EXTEND SEWER VENT 2' ABOVE EVAP. COOLER - EXTEND CONDENSATE DRAIN INTO GUTTER ON ROOF. - EXTEND WALK-IN COOLER DRAIN TO WITHIN 6" OF THE GROUND. SECURE TO WALL. - PROVIDE PROPER FITTING ON CONDENSATE ON ROOF - CAP OFF VENT IN WALK IN COOLER - SCREW VENT PIPE TO OUTLET ON OVEN SMOKER |