Permit: T07CM00827

Parcel: 113100050


Addresses:

2745 N CAMPBELL AV


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T07CM00827

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
07/18/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
07/16/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
PARTIAL INSPECTION ONLY
CHECK YOUR PLANS -- WIRING TO BE PER PLAN

1. MAKE UP AIR TO BE ENERGIZED WHEN EITHER HOOD
EX. FAN IS ENERGIZED
2. RE-ROUTE ALARM TRANSFORMER WIRE
3. PANEL DIRECTORIES NOT CORRECT
4. DEMO/COVER OLD WIRING
5. REPLACE DAMAGE APPLIANCE CORDS
6. RECEPTACLES WITH METAL FACEPLATES NEED TO EXTEND IN FRONT OF PLATES.
7. USE PROPER RACEWAY INTO COOLER AND SEAL RACEWAY
BOX OVERFILLED
8. PANEL A - LABEL "A"; USE MURRAY BREAKER, SEAL OPENINGS, PANEL DIRECTORY
9. ON ROOF - CONDENSOR NOT WIRED, IDENTIFY DISCONNECTS, STRAP FLEX, CHECK FUSING, ETC.
07/12/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
07/09/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
WORK NOT READY