Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T07CM00827
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/18/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
07/16/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* PARTIAL INSPECTION ONLY CHECK YOUR PLANS -- WIRING TO BE PER PLAN 1. MAKE UP AIR TO BE ENERGIZED WHEN EITHER HOOD EX. FAN IS ENERGIZED 2. RE-ROUTE ALARM TRANSFORMER WIRE 3. PANEL DIRECTORIES NOT CORRECT 4. DEMO/COVER OLD WIRING 5. REPLACE DAMAGE APPLIANCE CORDS 6. RECEPTACLES WITH METAL FACEPLATES NEED TO EXTEND IN FRONT OF PLATES. 7. USE PROPER RACEWAY INTO COOLER AND SEAL RACEWAY BOX OVERFILLED 8. PANEL A - LABEL "A"; USE MURRAY BREAKER, SEAL OPENINGS, PANEL DIRECTORY 9. ON ROOF - CONDENSOR NOT WIRED, IDENTIFY DISCONNECTS, STRAP FLEX, CHECK FUSING, ETC. |
|
07/12/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
07/09/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* WORK NOT READY |