Permit: T07CM00822

Parcel: 13316030E

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T07CM00822

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
05/01/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
04/26/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. INSTALL BATTERY BACKED BALLAST FOR EM LIGHT IN HALL PER PLANS.
2. NEED TO INSTALL PANEL DIRECTORY PER NEC 408.4
3. OK TO CLOSE CEILING HAVE LADDER AT NEXT INSPECTION TO CHECK EM LIGHT.