Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/11/2007 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* CORRECTIONS MADE FOR 6/11/07 INSPECTION |
|
| 07/10/2007 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. WIRING IS NOT PER PLAN -- WIRE PER PLAN OR REVISE PLAN TO SHOW ACTUAL SCOPE OF WORK. 2. EXPOSE ALL AREAS OF NEW WIRING FOR INSPECTION I WILL NOT ACCEPT PARTIAL AREAS UNLESS YOU CAN PROVIDE THE NAME OF THE ORIGINAL ELECTRICAL CONTRACTOR SO HE CAN GO OVER INSTALLATION WITH ME. 3. WATER BONDING CONDUCTOR FOR THIS UNITS SERVICE HAS BEEN STOLEN AND NEEDS TO BE REPLACED. |
|
| 06/11/2007 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. SUPPORT CONDUIT AS PER CODE 2. GROUND METAL BOXES 3. FULLY SEAT FITTING INTO BOX 4. PLANS STILL NOT REFLECTIVE OF LIGHTING INSTALLED VERIFY LIGHTING LOAD FOR CONTINUOUS TRAC 180VA/FOOT |
|
| 05/18/2007 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 04/19/2007 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* WORK COVERED PRIOR TO INSPECTION? IF WORK WAS INSPECTED UNDER ANOTHER PERMIT, PLEASE PROVIDE RESULTS. |