Permit: T07CM00821

Parcel: 12217002B


Addresses:

3447 E SPEEDWAY BL

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
07/11/2007 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
CORRECTIONS MADE FOR 6/11/07 INSPECTION
07/10/2007 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. WIRING IS NOT PER PLAN -- WIRE PER PLAN OR REVISE PLAN TO SHOW ACTUAL SCOPE OF WORK.
2. EXPOSE ALL AREAS OF NEW WIRING FOR INSPECTION
I WILL NOT ACCEPT PARTIAL AREAS UNLESS YOU CAN PROVIDE THE NAME OF THE ORIGINAL ELECTRICAL CONTRACTOR SO HE CAN GO OVER INSTALLATION WITH ME.
3. WATER BONDING CONDUCTOR FOR THIS UNITS SERVICE HAS BEEN STOLEN AND NEEDS TO BE REPLACED.
06/11/2007 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. SUPPORT CONDUIT AS PER CODE
2. GROUND METAL BOXES
3. FULLY SEAT FITTING INTO BOX
4. PLANS STILL NOT REFLECTIVE OF LIGHTING INSTALLED
VERIFY LIGHTING LOAD FOR CONTINUOUS TRAC 180VA/FOOT
05/18/2007 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
04/19/2007 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
WORK COVERED PRIOR TO INSPECTION?
IF WORK WAS INSPECTED UNDER ANOTHER PERMIT, PLEASE PROVIDE RESULTS.