Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/16/2007 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 06/25/2007 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* PROVIDE AIR BALANCE REPORT & REPORT FROM DUCT SMOKE DETECTOR TEST -- OK TO FILE FOR TEMP C OF O |
|
| 06/22/2007 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. A/C 12 PROVIDE A GAS SHUT OFF VALVE @ FLEX CONNECTOR REMOVE VENTS FROM CONDENSATE DRAINS OR INSTALL DOWNSTREAM OF THE TRAP. 2. PERMANENTLY I.D ALL UNITS ON ROOF 3. DO NOT RUN SEAL TITE THROUGH AN UNPROTECTED OPENING. 4. REPLACE ALL FLATTENED CONDENSATE TRAPS. 5. AC 2 CANNOT BE DOUBLE TRAPPED 6. AC 4 DOUBLE TRAPPED. DATA PLATE NOT IDENTIFIED FOR HEAT STRIP. REMOVE ALL DUPLICATE TRAPS. NO VENTS AHEAD OF TRAPS. DUCT DETECTORS NOT SHUTTING DOWN FANS. |