Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/30/2007 | MECHANICAL - ABOVE CEILING | Approved | IVRS - Inspection :* | |
| 05/25/2007 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1. OK TO SHEETROCK RESTROOMS 2. PROVIDE DUCTED RETURN AIR IN UNCONDITIONED ATTIC SPACES. 3. CONSULT ENGINEER & REVISE PLANS AS NECESSARY. |
|
| 05/24/2007 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* ROOM #325, 346, 311 RETURN AIR DUCT W/SMOKE DAMPERS IN THESE ROOMS EXHAUSTING INTO AREA ABOVE CEILING (THIS IS A PLENIUM) AND NEEDS TO BE FLAME SMOKE RATED OR DUCTED OUT OF PROJECTED PLENIUM. CONSULT ENGINEER FOR DIRECTION. PARTIAL SUSPENDED ROUGH DUCTS OVER RESTROOM CEILINGS. |