Permit: T07CM00812

Parcel: 141095990

Inspection Status: Approved

Inspection History: FRAMING

Date Description Inspector Results Comments
05/10/2007 FRAMING Approved IVRS - Inspection :*
05/01/2007 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) F-7 TRUSS NOTCHED 2 FT FROM NORTH END
2) 3/4" NOTCH BY 3 1/8" HOLE SPAN-PROVIDE ENGINEER REPAIR
3) OK TO INSULATE AND DRYWALL ALL BUT REPAIR AREA
04/30/2007 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) B-VENT OFF SET MUST BE MINIMUM 30 DEGREE PITCH
2) NO UFER
3) F-7 TRUSS NOTCHED BY PLUMBER AT TOILET 2 FT NORTH WALL PROVIDE ENGINEERING
4) CLIP GLB POST AT 1/2 BATH
5) LEAK AT TUB BASKET