Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
Permit Number - T07CM00809
Inspection Description - FRAMING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/18/2007 | FRAMING | Approved | IVRS - Inspection :* | |
04/17/2007 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NMC NOT ALLOWED FOR NEW WORK IN SPAS AND POOLS. MUST HAVE INSULATED GROUND SEE IRC TABLE E 41 02.1 2) HOLDOWN NOT INSTALLED |
|
04/13/2007 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. HOLD DOWN MISSING M.BATH SEE EXT. CLIP INSP. 2. POSSIBLE DWV LEAK M/BATH WEST FLOOR 3. WHAT IS 220 CABLE TO REAR OF HOUSE? NOT ON PLAN 4. UFER BAR OUT OF WALL |
|
04/12/2007 | FRAMING | Not ready for Inspection | IVRS - Inspection :* 1) NOT READY PER PETE |