Permit: T07CM00809

Parcel: 141095890

Inspection Status: Approved

Inspection History: FRAMING

Permit Number - T07CM00809

Inspection Description - FRAMING

Inspection Status - Approved

Date Description Inspector Results Comments
04/18/2007 FRAMING Approved IVRS - Inspection :*
04/17/2007 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) NMC NOT ALLOWED FOR NEW WORK IN SPAS AND POOLS. MUST HAVE INSULATED GROUND SEE IRC TABLE E 41 02.1
2) HOLDOWN NOT INSTALLED
04/13/2007 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. HOLD DOWN MISSING M.BATH SEE EXT. CLIP INSP.
2. POSSIBLE DWV LEAK M/BATH WEST FLOOR
3. WHAT IS 220 CABLE TO REAR OF HOUSE? NOT ON PLAN
4. UFER BAR OUT OF WALL
04/12/2007 FRAMING Not ready for Inspection IVRS - Inspection :*
1) NOT READY PER PETE