Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/15/2010 | BUILDING - FINAL | Approved | IVRS - Inspection :* | |
| 10/13/2009 | BUILDING - FINAL | Denied | 1) BOND WATER PIPING AT WATER HEATER 2) TPRV DISCHARGE LINE TRAPPED-MUST FLOW DOWN HILL TO DAY LIGHT 3) DEAD FRONT MISSING IN SUB PANEL 4) PANEL SCHEDULE REQUIRED IN SUB PANEL 5) DISCONNECT FOR WATER HEATER MISSING IN SERVICE PANEL 6) NM CABLE FROM OUTLET TO WATER HEATER MUST BE PROTECTED 7) PROVIDE GAS PRESSURE TEST |