Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T07CM00795
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/31/2007 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
08/03/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* PREVIOUS INSPECTION ITEMS CORRECTED |
|
08/01/2007 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
06/26/2007 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. CABLES TO BE SECURED TO BOX 312.5 -- DO NOT BRAKE OUT BOX CLAMPS 2. WHO IS QUALIFIED ELECTRICIAN |
|
06/18/2007 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : There is no access to the site.| 920* CALLED NUMBER AND NOT IN SERVICE LOCKED NO ACCESS |
|
04/20/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK WALL COVER BATHROOM BOX OUTSIDE BATH OVERFILLED - CHANGE NOTE: WALL PARTIALLY COVERED @ INSPECTION PROVIDE NAME OF ELECTRICAL CONTRACTOR EXTERIOR SWITCHES TO BE RELOCATED |
|
04/09/2007 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
04/06/2007 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) OPEN WALLS AS DIRECTED 2) PLEASE PROVIDE PLANS FOR ELECTRIC-NEW SWITCHES, LIGHTS AND RECEPTACLES FOR WALLS AND BATHROOM 3) MAINTAIN WORKING CLEARANCE 110.26 |