Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/31/2007 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 12/28/2007 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* DUCT STILL APPEARS TO BE RESTRICTED. PLEASE PROVIDE BALANCE REPORT TO VERIFY PROPER AIRFLOW IS AVAILABLE |
|
| 12/27/2007 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 11/30/2007 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* - PROVIDE R-8 INSULATION AT ROOFTOP DUCTWORK - RTU-3 RETURN AIR DUCT IS RESTRICTED - PROVIDE PROPER CLEARANCE OF OUTSIDE AIR INTAKE TO WASTE VENT ON RTU-3 |
|
| 11/20/2007 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 10/19/2007 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* VERIFY HEAT STRIPS, WIRE & FUSE SIZES PROVIDE OUTSIDE AIR & BALANCE PER PLANS PROVIDE AIR BALANCE REPORT |