Permit: T07CM00784

Parcel: 12314126D


Addresses:

711 E LESTER ST

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
12/31/2007 MECHANICAL - FINAL Approved IVRS - Inspection :*
12/28/2007 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
DUCT STILL APPEARS TO BE RESTRICTED. PLEASE PROVIDE BALANCE REPORT TO VERIFY PROPER AIRFLOW IS AVAILABLE
12/27/2007 MECHANICAL - FINAL Not ready for Inspection IVRS - Inspection :*
11/30/2007 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
- PROVIDE R-8 INSULATION AT ROOFTOP DUCTWORK
- RTU-3 RETURN AIR DUCT IS RESTRICTED
- PROVIDE PROPER CLEARANCE OF OUTSIDE AIR INTAKE
TO WASTE VENT ON RTU-3
11/20/2007 MECHANICAL - FINAL Not ready for Inspection IVRS - Inspection :*
10/19/2007 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
VERIFY HEAT STRIPS, WIRE & FUSE SIZES

PROVIDE OUTSIDE AIR & BALANCE PER PLANS
PROVIDE AIR BALANCE REPORT