Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/04/2007 | PLUMBING - FINAL | Approved | IVRS - Inspection :* 1. CORRECTIONS MADE OK 2. INSTALLED PER REDLINES OK SUBJECT TO ARCHITECT/OWNER APPROVED OF VANITY LAVS 3. PLUMBING FINAL OK |
|
| 11/29/2007 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* SEE 409.1 2003 UPC ELONGATED 409.22 2003 UPC SEATS OPEN FRONT - WATER COOLER NOT INSTALLED PER PLAN - COVERED W/O INSPECTION - ABS NOT PERMITTED IN EXTERIOR LOCATION ABOVE GRADE - SANTEE NOT PERMITTED ON ITS BACK - PLAN SHOWS REVENT - NOT AAV - TEMPERING VALVE NOT ACCESSIBLE FOR SERVICING - EXPANSION TANK NOT SUPPORTED - HOT PIPING NOT INSULATED - PAN DRAIN MAY NOT BE REDUCED - MAY NOT BE A COMPLETE LIST |