Permit: T07CM00784

Parcel: 12314126D


Addresses:

711 E LESTER ST

Inspection Status: Approved

Inspection History: PLUMBING - ROUGH, SOIL

Date Description Inspector Results Comments
09/10/2007 PLUMBING - ROUGH, SOIL Approved OK FOR CONCRETE
09/04/2007 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
OK TO COVER, RECALL INSP. PRIOR TO CONCRETE
08/29/2007 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
1. TEST BALL BLEW
2. INSTALLATION OK
NEED TO SEE ACCURATE REDLINES BEFORE YOU COVER
08/28/2007 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
08/23/2007 PLUMBING - ROUGH, SOIL Not ready for Inspection IVRS - Inspection :*
1. A COMBO IS NOT THE CORRECT FITTING FOR A TRAP ARM
THE POINT OF VENT IS BELOW THE TRAP WEIR
2. WET VENTED SECTION TO BE 3" (ONE PIPE SIZE LARGER THAN REQUIRED DRAIN SIZE OF UPPER FIXTURE)
3. ALL DRAINAGE PIPING TO HAVE 2% PITCH CONTINUED "NOT READY" WILL RESULT IN A REINSPECTION FEE.
08/22/2007 PLUMBING - ROUGH, SOIL Not ready for Inspection IVRS - Inspection :*
1. NOT INSTALLED PER PLAN BECAUSE YOU EXTENDED THE 4" PAST THE LAST WATER CLOSET, YOU MUST PROVIDE A FULL SIZE CLEANOUT FOR THAT SECTION OF PIPE.
2. FOR DRAINAGE PIPING: DBL SANTEE MAY BE USED WHEN BARREL OF FITTING IS TWO PIPE SIZES LARGER THAN LARGEST INLET.
3. FOR BACK TO BACK FIXTURES DBL SANTEE IS NOT PERMITTED.