Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - ROUGH, SOIL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/10/2007 | PLUMBING - ROUGH, SOIL | Approved | OK FOR CONCRETE | |
| 09/04/2007 | PLUMBING - ROUGH, SOIL | Partial Approval | IVRS - Inspection :* OK TO COVER, RECALL INSP. PRIOR TO CONCRETE |
|
| 08/29/2007 | PLUMBING - ROUGH, SOIL | Partial Approval | IVRS - Inspection :* 1. TEST BALL BLEW 2. INSTALLATION OK NEED TO SEE ACCURATE REDLINES BEFORE YOU COVER |
|
| 08/28/2007 | PLUMBING - ROUGH, SOIL | Partial Approval | IVRS - Inspection :* | |
| 08/23/2007 | PLUMBING - ROUGH, SOIL | Not ready for Inspection | IVRS - Inspection :* 1. A COMBO IS NOT THE CORRECT FITTING FOR A TRAP ARM THE POINT OF VENT IS BELOW THE TRAP WEIR 2. WET VENTED SECTION TO BE 3" (ONE PIPE SIZE LARGER THAN REQUIRED DRAIN SIZE OF UPPER FIXTURE) 3. ALL DRAINAGE PIPING TO HAVE 2% PITCH CONTINUED "NOT READY" WILL RESULT IN A REINSPECTION FEE. |
|
| 08/22/2007 | PLUMBING - ROUGH, SOIL | Not ready for Inspection | IVRS - Inspection :* 1. NOT INSTALLED PER PLAN BECAUSE YOU EXTENDED THE 4" PAST THE LAST WATER CLOSET, YOU MUST PROVIDE A FULL SIZE CLEANOUT FOR THAT SECTION OF PIPE. 2. FOR DRAINAGE PIPING: DBL SANTEE MAY BE USED WHEN BARREL OF FITTING IS TWO PIPE SIZES LARGER THAN LARGEST INLET. 3. FOR BACK TO BACK FIXTURES DBL SANTEE IS NOT PERMITTED. |