Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/28/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 11/20/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* PARTIAL INSPECTION - REINSPECTION FEE TO BE PAID 1. SERVICE DISCONNECTS STILL NOT IDENTIFIED - NEC 230.70B 2. BOND FOR WATER STILL UNDERSIZED - NEC 250.104 A1 3. STILL NEED TO REMOVE UNUSED FEEDER TAPS IN GUTTER 4. PANEL "B" TO HAVE 200 AMP CKT PER PLAN/YOU HAVE 125 AMP FUSE? 5. IDENTIFY PANEL "A" CIRCUIT DIRECTORY - NOT SHARPIE NEC 408.4 6. IDENTIFY WHAT PANEL IS "A" AND WHAT IS "B" 7. ALL LOADS TO ORIGINATE FROM PANELS AS SHOWN ON PLAN 8. MULTI-WIRE BRANCH CKT PHASE CONDUCTORS TO TERMINATE ON SEPARATE PHASES 9. EQUIPMENT GROUNDS #6 & SMALLER TO BE GREEN ENTIRE LENGTH - DO NOT TAPE NEC 250.119 10. PANEL DIRECTORY'S TO BE IDENTIFIED CORRECTLY, CLEARLY AND LEGIBLE PREVIOUS INSPECTION CORRECTIONS TO BE COMPLETED PROVIDE LADDER TO ROOF |
|
| 11/14/2007 | ELECTRIC - FINAL | Cancelled | IVRS - RI canceled | |
| 10/17/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* IN SERVICE GUTTER - 1. ILSCO TAPS TO BE PROPERLY INSULATED TO AVOID CONTACT WITH GROUNDED PARTS (BOLT HEADS ARE HOT) REMOVE UNUSED FEEDER TAPS, ALSO, NEED WEATHERPROOF K.O SEALS SERVICE - 1. WIRING NOT PER PLAN. PLANS CALL FOR 400 AMP PANEL AND ANOTHER DISCONNECT TO FIRE ALARM PANEL. ALL SERVICE DISCONNECTS ARE TO BE IDENTIFIED AS "SERVICE DISCONNECT" 2. SERVICE NIPPLE TO PANEL TO BE BONDED 3. INDOOR PANEL TO HAVE PROPER FRONT WORKING CLEARANCE 4. BOND FOR WATER PIPE UNDERSIZED INSIDE - 1. WATER HEATER NOT SIZED PER PLAN, ACCESS PANELS TO BE ACCESSIBLE FOR WATER HEATER 2. PANEL DIRECTORY TO BE CLEAR, CORRECT AND LEGIBLE HVAC - 1. GROUND GUTTER 2. HEAT STRIPS TO BE INSTALLED PER PLAN AND DATA CABLE IDENTIFIED MAKE SURE UNITS HAVE PROPERLY SIZED CONDUCTORS AND OVERCURRENT PROTECTION. 3. SECURE EMT TO ROOF, STRAP FLEX WITHIN 12" OF TERMINATIONS 4. IDENTIFY DISCONNECTS (I.E #1,2,3) 5. SERVICE RECEPTACLE TO BE WITHIN 25' OF UNITS 6. THE 2 WEST DISCONNECTS TO HAVE PROPER FRONT WORKING CLEARANCE, EMT NOT TO RUN IN FRONT OF FIRE ALARM NOT COMPLETE - PARTIAL INSPECTION |
|
| 10/09/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : Work is not complete enough to inspect.| 950* PARTIAL INSPECTION - NOT A COMPLETE LIST 1. MECHANICAL ON ROOFTOP NOT COMPLETE 2. WATER HEATER NOT IN YET 3. AT SERVICE - GROUNDING ELECTRODE CONDUCTOR AND BONDING (WATER) IS MISSING. DISCONNECTS MISSING HANDLES, IDENTIFY ALL EQUIPMENT 4. FIRE ALARM NOT IN/NOT PERMITTED 5. WIRING TO BE PER PLAN 6. BOND SERVICE NIPPLE 7. NEED BOX EXTENDERS PARTIAL INSPECTION ONLY WORK NOT COMPLETE ENOUGH TO INSPECT FOR FINAL - DO NOT CALL BEFORE READY. |