Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/09/2007 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 08/06/2007 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 3-COMP SINK WALL RESTROOM LAV DRAINAGE TO BE 1 1/2 NOT TO EXCEED 42" DRAIN ARM OTHER RESTROOM LAV DRAINAGE TO HAVE MINIMUM FALL 1/4" PER FOOT AND BE 1 1/2 DRAIN ARM. PERM CAPS REQUIRED ON DEMO AS PER 8/3/07 INSP. DOUBLE VENT AT 3-COMP SINK AREA IS FOR ? AND DOES NOT MEET 2003 UPC REQUIREMENTS. OK TO COVER NORTH RESTROOMS, P-3 SINK P-4 MOP SINK FOR PLUMBING |
|
| 08/03/2007 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* - USE 03050 FOR GAS PIPE INSPECTIONS - GAS PIPING NOT SIZED PER PLAN. ALSO, 3 1/2" REQUIRED ABV ROOF. - WATER PIPING NOT SIZED PER PLAN, SEE FIXTURE SCHEDULE. - WASTE & VENT NOT PER PLAN. REDLINE PLAN TO CONTINUE. - PLAN REVISION REQUIRED FOR GW, DF, ABS AND AAV AT P-3 - CORRECT SLOPE AT TIE IN - CORRECT UNVENTED FS - PROPERLY INSTALL DRAINAGE FITTINGS - PROPERLY INSTALL TRAP ARMS - PERM CAPS REQUIRED ON DEMO - BACKFLOW PREVENTER REQUIRED FOR IRRIGATION |