Permit: T07CM00779

Parcel: 141330070


Addresses:

8454 S HUNNIC DR


Inspection Status: Approved

Inspection History: EXT METAL CLIPS/EXT SHEATHING

Permit Number - T07CM00779

Inspection Description - EXT METAL CLIPS/EXT SHEATHING

Inspection Status - Approved

Date Description Inspector Results Comments
05/02/2007 EXT METAL CLIPS/EXT SHEATHING Approved IVRS - Inspection :*
04/30/2007 EXT METAL CLIPS/EXT SHEATHING Not ready for Inspection IVRS - Inspection :*
1) CANCELLED PER SUPER
04/26/2007 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) NEED WIND BRACE NORTH WEST CORNER 1ST FLOOR
2) TOO MUCH NAILING MISSED, TOO MANY SHINNERS
3) ALL FRIEZE MISSED NAILS (SHINNERS)
4) WRONG NAILS IN SOME P.A. STRAPS
5) SHEAR PAGE 2ND FLOOR SHEAR TO LAP OUTSIDE WALL-SEE PLAN
6) AT 2ND FLOOR 1ST-2ND FLOOR STRAPS AT CORNERS OF SHEARWALL
7) STRAP COLUMN TO REAR PORCH BEAM
8) X BRACE TRUSSES WEST END OF VERT. MEMBERS
9) TWO BROKEN TRUSSES SEE MARK ON FLOOR
10) OSB AT FRONT COLUMN OR DBL STUD
11) MISSING HANGERS AT TRUSS TO GIRDER WORNG NAILS IN LOAD BEARING HANGERS