Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/09/2008 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* | |
| 01/08/2008 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. NEED CORRECT SIZE BOND CLAMP TO GAS PIPE 2. REMOVE ABANDONED EQUIPMENT 3. IDENTIFY SUB-PANEL FEEDER NEUTRAL 4. STRANDED CONDUCTOR NOT ALLOWED UNDER GROUND SCREW 5. PROVIDE ATTIC ACCESS |
|
| 11/07/2007 | ELECTRIC - SERVICE UPGRADE | Partial Approval | IVRS - Inspection :* 1. EXTEND GROUNDING ELECTRODE TO SERVICE & PANEL K 2. NEED PROPERLY SIZED GAS BOND CLAMP |
|
| 11/06/2007 | ELECTRIC - SERVICE UPGRADE | Not ready for Inspection | IVRS - Inspection :* CORRECTIONS NOT COMPLETE |
|
| 11/02/2007 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* PARTIAL INSPECTION ONLY 1. IDENTIFY SERVICE NEUTRAL AT BOTH ENDS WITH WHITE TAPE - NEC 200 2. BOND SERVICE MAST - NEC 250.92 3. ARRANGE BONDING CONDUCTORS TO PREVENT OBJECTIONABLE CURRENT - NEC 250.6 4. IDENTIFY SERVICE DISCONNECTS - NEC 230.70 AND INSTALL ADDRESS LABEL 5. INSTALL GROUNDING ELECTRODE SYSTEM FOR SERVICE & BOND PIPING - NEC 250 6. BONDING CONDUCTORS FOR SERVICE RACEWAYS UNDERSIZED - NEC 250.102D 7. INSTALL FEEDER, PANEL & FUSES |
|
| 10/02/2007 | ELECTRIC - SERVICE UPGRADE | Cancelled | IVRS - RI canceled | |
| 09/27/2007 | ELECTRIC - SERVICE UPGRADE | Cancelled | IVRS - RI canceled | |
| 09/07/2007 | ELECTRIC - SERVICE UPGRADE | Not ready for Inspection | IVRS - Inspection :* PLANS TO BE REVISED AND RE- APPROVED TO SHOW ACTUAL SCOPE OF WORK |