Permit: T07CM00778

Parcel: 124020450


Addresses:

1621 E 1ST ST

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
01/09/2008 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection :*
01/08/2008 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. NEED CORRECT SIZE BOND CLAMP TO GAS PIPE
2. REMOVE ABANDONED EQUIPMENT
3. IDENTIFY SUB-PANEL FEEDER NEUTRAL
4. STRANDED CONDUCTOR NOT ALLOWED UNDER GROUND SCREW
5. PROVIDE ATTIC ACCESS
11/07/2007 ELECTRIC - SERVICE UPGRADE Partial Approval IVRS - Inspection :*
1. EXTEND GROUNDING ELECTRODE TO SERVICE & PANEL K
2. NEED PROPERLY SIZED GAS BOND CLAMP
11/06/2007 ELECTRIC - SERVICE UPGRADE Not ready for Inspection IVRS - Inspection :*
CORRECTIONS NOT COMPLETE
11/02/2007 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
See detailed listing on site.| 999*
PARTIAL INSPECTION ONLY
1. IDENTIFY SERVICE NEUTRAL AT BOTH ENDS
WITH WHITE TAPE - NEC 200
2. BOND SERVICE MAST - NEC 250.92
3. ARRANGE BONDING CONDUCTORS TO PREVENT OBJECTIONABLE CURRENT - NEC 250.6
4. IDENTIFY SERVICE DISCONNECTS - NEC 230.70 AND INSTALL ADDRESS LABEL
5. INSTALL GROUNDING ELECTRODE SYSTEM FOR SERVICE & BOND PIPING - NEC 250
6. BONDING CONDUCTORS FOR SERVICE RACEWAYS UNDERSIZED - NEC 250.102D
7. INSTALL FEEDER, PANEL & FUSES
10/02/2007 ELECTRIC - SERVICE UPGRADE Cancelled IVRS - RI canceled
09/27/2007 ELECTRIC - SERVICE UPGRADE Cancelled IVRS - RI canceled
09/07/2007 ELECTRIC - SERVICE UPGRADE Not ready for Inspection IVRS - Inspection :*
PLANS TO BE REVISED AND RE- APPROVED TO SHOW ACTUAL SCOPE OF WORK