Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - HOODS
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/04/2007 | MECHANICAL - HOODS | Approved | IVRS - Inspection :* | |
| 08/28/2007 | MECHANICAL - HOODS | Partial Approval | IVRS - Inspection :* CHECKED EXHAUST DUCTS FROM PAN WASHER & DISHWASHER STILL NEED TO SEE MAKE UP AIR UNIT |
|
| 08/06/2007 | MECHANICAL - HOODS | Partial Approval | IVRS - Inspection :* CHECKED FINAL WELDS ON GREASE DUCTS OK TO FIRE WRAP |
|
| 08/03/2007 | MECHANICAL - HOODS | Partial Approval | IVRS - Inspection :* CHECKED WELDS ON GREASE DUCT DELI OK TO FIRE WRAP HAVE YOUR ARCHITECT DESIGN A MAKE UP AIR SYSTEM THAT COMPLIES WITH SECTION 508.1.1 IMC |
|
| 07/13/2007 | MECHANICAL - HOODS | Partial Approval | IVRS - Inspection :* BAKERY OVEN OK TO ENERGIZE |