Permit: T07CM00754

Parcel: 11460019C

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T07CM00754

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
03/14/2008 ELECTRIC - FINAL Approved PER INSP CARD
01/15/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
AS BUILTS NOT CORRECT TO WORK INSTALLED - PANEL J & 5B
90 DAYS TO CORRECT
09/12/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. WEATHERPROOF RECEPTACLE COVER TO BE WEATHERPROOF WHETHER OR NOT PLUGGED INTO -- 406.8
2. LABEL UNITS
3. GROUND JUNCTION BOXES
4. USE TERMINAL END WITH STRANDED WIRE
5. FINISH VDV CABELING
6. NEED AS-BUILT PLANS TO HAVE CITY APPROVED PLAN CHECK STAMP
7. #4 OF PREVIOUS INSPECTION
09/10/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
OK SQUARE "D" LETTER FOR SERVICING OF MAIN DISCONNECTING MEANS

1. PANEL SCHEDULES TO BE AS PER 408.4 --
NO ABBREVIATIONS
2. SUPPORT VDV CABLING 725.6, 800.6, 300.11
3. MC TO BE AS PER 300.11
4. PLEASE VERIFY MAGAZINE RACK LIGHT LISTING
5. EXTERIOR RING BREAKROOM
6. SECURE FIXTURES TO GRID MOR OFFICE
09/05/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. MAINTAIN WORKING SPACE AT ALL TIMES IN FRONT OF EQUIPMENT
2. SUPPORT VDV CABLING AS PER 725.6
3. FILL UNUSED OPENINGS & INSTALL MISSING COVERS
4. CLEAN EXCESS FOREIGN MATERIAL FROM PANELS 110.12
5. CORRECTLY IDENTIFY GROUNDED CONDUCTORS 200.6
6. CORRECTLY IDENTIFY DISCONNECT
08/14/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. ATTACH FIXTURES TO GRID 410.16
2. SUPPORTS & WIRES TO BE AS PER 300.11
3. LABEL DISCONNECT

OK WALLS MANAGERS OFFICE & BREAKROOM
OK BAKERY FREEZER
08/10/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
08/08/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
08/07/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
08/03/2007 ELECTRIC - FINAL Partial Approval 1. 1 G RECEPTACLES AT CUSTOMER SERVICE MISSING ISOLATED GROUNDING CONDUCTOR - ALSO, IDENTIFY CONDUCTOR.
2. VDV CABELING ABOVE CUSTOMER SERVICE TO BE AS PER 725.3 & 6, 800.3 & 6,
ALSO, DELI PREP
3. SUPPORT WIRES NEEDED FOR CAN LIGHTS
4. SUPPORT MC CABLES UP OFF OF GRID
OK REGULAR POWER CUSTOMER SERVICE
OK FLOOR CASES & DELI CASES - DELI PREP
OK GFCI'S DELI PREP
OK TRAC LIGHTS DELI PREP

RECEIVED CK#2093 FOR $108.00
08/03/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
07/20/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
AREAS NOT TO BE OCCUPIED UNTIL PARTIAL FINALED BY INSPECTION

1. PLANS NOT REFLECTIVE AT BAKERY OVEN
INSTALL AS PER PLANS OR REVISE & RESTRAP PLANS
(CITY STAMP)
2. SUPPORT CONDUITS AS DISCUSSED

OK BAKERY OVEN TEMP USAGE UNTIL ARCHITECT REVISIONS
OK DELI STORAGE WALL & BAKERY PREP WALL
07/11/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
OK MEAT CASE
OK FROZEN SEAFOOD
OK FLORAL REACH IN

1. INSTALL COVERS AT MEAT/SEAFOOD
07/10/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. CORD NOT ALLOWED ABOVE CEILING -- 400.7 & 8
2. SUPPORT FLEX BEFORE DOWN WALL
3. BOXES ON TOP OF FLORAL REACH IN OVERFILLED -- 312.16
4. TIGHTEN GROUND BARS MEAT CASE

OK FLORAL KIOSK
OK TRAC'S AT BALLOONS
07/09/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
OK FLORAL WALK IN BOX
1. RESEAT FLEX CONDUITS INTO FITTINGS
2. TIGHTEN LOOSE FITTINGS AT FLOOR - FLORAL
3. SUPPORT CONDUIT IN WALLS
4. SUPPORT TRAC LIGHTING INDEPENDENTLY 1/4' SECTION
06/27/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
06/26/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. VDV CABELING TO BE AS PER 725.3 & 6, 800.3 & 6
2. SUPPORT CONDUITS ON THE VERTICALS
3. VERIFY CLAMP LISTING FOR ALL THREAD

OK PRODUCE & SALAD CASES

RECEIVED CHECK #2087 FOR $108.00
06/21/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
OK BOXES ABOVE DAIRY BOX FOR SEALING
OK LUNCH MEAT, BEVERAGE AND DAIRY CASES

RECEIVED CK#2086 FOR $108.00
06/20/2007 ELECTRIC - FINAL Partial Approval OK DAIRY CASES
OK DAIRY BOX
1. FILL INSIDE CONDUIT AT ENTRANCE TO DAIRY BOX WITH A NON-COMBUSTIBLE PRODUCT - 300.7
2. GROUND JUNCTION BOXES - ABOVE DAIRY BOX
3. SUPPORT CONDUIT DOWN TO DAIRY CASE

RECEIVED CHECK #2085 FOR $108.00
06/13/2007 ELECTRIC - FINAL Partial Approval OK ISLE 8 FROZEN CASE

RECEIVED CHECK #2082 FOR $108.00
06/12/2007 ELECTRIC - FINAL Partial Approval OK FROZEN MEAT CASE

RECEIVED CK#2081 FOR $108.00
06/08/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
OK CASES ISLE 7 & 8 AND END CAP

SPOKE W/MANAGER AND ACTING SUPERINTENDENT ABOUT SECURING AREAS IN CONSTRUCTION FROM GENERAL PUBLIC NOTIFIED LEE RAY

RECEIVED CHECK #2080 FOR $108.00
06/07/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*