Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T07CM00754
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/14/2008 | ELECTRIC - FINAL | Approved | PER INSP CARD | |
01/15/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* AS BUILTS NOT CORRECT TO WORK INSTALLED - PANEL J & 5B 90 DAYS TO CORRECT |
|
09/12/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. WEATHERPROOF RECEPTACLE COVER TO BE WEATHERPROOF WHETHER OR NOT PLUGGED INTO -- 406.8 2. LABEL UNITS 3. GROUND JUNCTION BOXES 4. USE TERMINAL END WITH STRANDED WIRE 5. FINISH VDV CABELING 6. NEED AS-BUILT PLANS TO HAVE CITY APPROVED PLAN CHECK STAMP 7. #4 OF PREVIOUS INSPECTION |
|
09/10/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* OK SQUARE "D" LETTER FOR SERVICING OF MAIN DISCONNECTING MEANS 1. PANEL SCHEDULES TO BE AS PER 408.4 -- NO ABBREVIATIONS 2. SUPPORT VDV CABLING 725.6, 800.6, 300.11 3. MC TO BE AS PER 300.11 4. PLEASE VERIFY MAGAZINE RACK LIGHT LISTING 5. EXTERIOR RING BREAKROOM 6. SECURE FIXTURES TO GRID MOR OFFICE |
|
09/05/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. MAINTAIN WORKING SPACE AT ALL TIMES IN FRONT OF EQUIPMENT 2. SUPPORT VDV CABLING AS PER 725.6 3. FILL UNUSED OPENINGS & INSTALL MISSING COVERS 4. CLEAN EXCESS FOREIGN MATERIAL FROM PANELS 110.12 5. CORRECTLY IDENTIFY GROUNDED CONDUCTORS 200.6 6. CORRECTLY IDENTIFY DISCONNECT |
|
08/14/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. ATTACH FIXTURES TO GRID 410.16 2. SUPPORTS & WIRES TO BE AS PER 300.11 3. LABEL DISCONNECT OK WALLS MANAGERS OFFICE & BREAKROOM OK BAKERY FREEZER |
|
08/10/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* | |
08/08/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* | |
08/07/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* | |
08/03/2007 | ELECTRIC - FINAL | Partial Approval | 1. 1 G RECEPTACLES AT CUSTOMER SERVICE MISSING ISOLATED GROUNDING CONDUCTOR - ALSO, IDENTIFY CONDUCTOR. 2. VDV CABELING ABOVE CUSTOMER SERVICE TO BE AS PER 725.3 & 6, 800.3 & 6, ALSO, DELI PREP 3. SUPPORT WIRES NEEDED FOR CAN LIGHTS 4. SUPPORT MC CABLES UP OFF OF GRID OK REGULAR POWER CUSTOMER SERVICE OK FLOOR CASES & DELI CASES - DELI PREP OK GFCI'S DELI PREP OK TRAC LIGHTS DELI PREP RECEIVED CK#2093 FOR $108.00 |
|
08/03/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
07/20/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* AREAS NOT TO BE OCCUPIED UNTIL PARTIAL FINALED BY INSPECTION 1. PLANS NOT REFLECTIVE AT BAKERY OVEN INSTALL AS PER PLANS OR REVISE & RESTRAP PLANS (CITY STAMP) 2. SUPPORT CONDUITS AS DISCUSSED OK BAKERY OVEN TEMP USAGE UNTIL ARCHITECT REVISIONS OK DELI STORAGE WALL & BAKERY PREP WALL |
|
07/11/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* OK MEAT CASE OK FROZEN SEAFOOD OK FLORAL REACH IN 1. INSTALL COVERS AT MEAT/SEAFOOD |
|
07/10/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. CORD NOT ALLOWED ABOVE CEILING -- 400.7 & 8 2. SUPPORT FLEX BEFORE DOWN WALL 3. BOXES ON TOP OF FLORAL REACH IN OVERFILLED -- 312.16 4. TIGHTEN GROUND BARS MEAT CASE OK FLORAL KIOSK OK TRAC'S AT BALLOONS |
|
07/09/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* OK FLORAL WALK IN BOX 1. RESEAT FLEX CONDUITS INTO FITTINGS 2. TIGHTEN LOOSE FITTINGS AT FLOOR - FLORAL 3. SUPPORT CONDUIT IN WALLS 4. SUPPORT TRAC LIGHTING INDEPENDENTLY 1/4' SECTION |
|
06/27/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* | |
06/26/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. VDV CABELING TO BE AS PER 725.3 & 6, 800.3 & 6 2. SUPPORT CONDUITS ON THE VERTICALS 3. VERIFY CLAMP LISTING FOR ALL THREAD OK PRODUCE & SALAD CASES RECEIVED CHECK #2087 FOR $108.00 |
|
06/21/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* OK BOXES ABOVE DAIRY BOX FOR SEALING OK LUNCH MEAT, BEVERAGE AND DAIRY CASES RECEIVED CK#2086 FOR $108.00 |
|
06/20/2007 | ELECTRIC - FINAL | Partial Approval | OK DAIRY CASES OK DAIRY BOX 1. FILL INSIDE CONDUIT AT ENTRANCE TO DAIRY BOX WITH A NON-COMBUSTIBLE PRODUCT - 300.7 2. GROUND JUNCTION BOXES - ABOVE DAIRY BOX 3. SUPPORT CONDUIT DOWN TO DAIRY CASE RECEIVED CHECK #2085 FOR $108.00 |
|
06/13/2007 | ELECTRIC - FINAL | Partial Approval | OK ISLE 8 FROZEN CASE RECEIVED CHECK #2082 FOR $108.00 |
|
06/12/2007 | ELECTRIC - FINAL | Partial Approval | OK FROZEN MEAT CASE RECEIVED CK#2081 FOR $108.00 |
|
06/08/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* OK CASES ISLE 7 & 8 AND END CAP SPOKE W/MANAGER AND ACTING SUPERINTENDENT ABOUT SECURING AREAS IN CONSTRUCTION FROM GENERAL PUBLIC NOTIFIED LEE RAY RECEIVED CHECK #2080 FOR $108.00 |
|
06/07/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* |