Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T07CM00754
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/14/2008 | ELECTRIC - INTERMEDIATE | Approved | PER INSP CARD | |
09/05/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
08/14/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
08/10/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK CUSTOMER SERVICE ISOLATED GROUNDS 2) OK CONTACTORS FOR HOODS 3) FINISH GROUNDING ALL METAL BOXES ON HOODS |
|
08/09/2007 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : Work is not complete enough to inspect.| 950* FINISH PREVIOUS ITEM |
|
08/08/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. CLEAN SURFACE UNDER GROUND BAR 250.12 2. CORRECTLY IDENTIFY UNGROUNDED CONDUCTORS 3. CORRECTLY GROUND JUNCTION BOXES OK HOODS SUBJECT TO CORRECTIONS |
|
08/07/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* RECEIVED CK#2094 FOR $108.00 OK DELI LINE 1. VERIFY LISTING/LABELING - BELSHAW 2. FINISH IG CIRCUITS AT CUSTOMER SERVICE - 250.119 |
|
08/03/2007 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
08/02/2007 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* DELI AREA OCCUPIED WITHOUT INSPECTION - VACATE AREA TO INSPECT 1. SCREW FOR FACE PLATE STRIPPED 2. BOX OVERFILLED CASES 3. DELI PREP RECEPTACLES TO BE GFCI PER 210.8(B) |
|
07/31/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | MAIN SWITCH IS INOPERABLE - IT WILL NEED TO BE WORKING FOR FINAL OK TO BE RE-ENERGIZED OK SWITCH ADDED TO SES OK BAKERY CAKE CASE RECEIVED CK#2092 FOR $108.00 |
|
07/30/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK WALL AT CUSTOMER SERVICE OK DELI, COOLER, FREEZER, BAKERY RETARDER BAKERY CASE: 1. TIGHTEN LOOSE FITTINGS 2. BOX IS OVERFILLED |
|
07/25/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. OK WALL AT DELI 2. OK (5) 3/4" EMT IN WALL FOR DELI CASE LINE UP 3. OK GFI RECEPT BAKERY COUNTER 4. OK SALES FLOOR STRAP LIGHTING 5. OK RECESSED FIXTURES AT MEAT/BAKERY DEPT |
|
07/23/2007 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* CANCELLED |
|
07/20/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
07/16/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. SUPPORT CONDUITS WITHIN 3' OF PANEL & BOXES 2. FILL UNUSED OPENING PANEL OK WALLS PANEL ROOM PANELS BP & BPB |
|
07/13/2007 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
07/11/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
07/10/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
07/09/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
06/29/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK UNDERGROUND PVC CONDUITS DELI & BAKERY OK CONDUITS ON RACK FROM PANELS "L1" & "L2" OK WALL CONDUITS PANELS "BP" & "BPV" |
|
06/27/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK PRODUCE WET RACK 1. STRAP CONDUITS AS PER CODE - BURY 10' 2. CHECK LARGE FITTINGS SET SCREWS REC'D CHECK #2089 FOR $108.00 |
|
06/26/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
06/21/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
06/20/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | ||
06/14/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK PVC CONDUIT PRODUCE 2) OK STARBUCK KIOSK 2) SECURE CAN LIGHTS 3) REMOVE UNUSED CABLES |
|
06/07/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | 1. BREAKER AMPACITY TO MATCH CONDUCTOR SIZES 2. FINISH SUPPORTING CONDUIT TO CASES 3. CONTRACTOR TO MAINTAIN LOCKOUT/TAG OUT PROCEDURES FOR ELECTRICAL EQUIPMENT. PLEASE PROVIDE A COPY OF PROCEDURE TO BE KEPT ON JOB. OK BEVERAGE CASE & FROZEN FOODS RECEIVED CHECK #2079 FOR $108.00 |
|
06/05/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. SUPPORT CONDUIT & FLEX TO CASES AS PER CODE 2. PLEASE OPEN UP CASE TO INSPECT TERMINATIONS & GROUNDING FOR AFTER/BEFORE HOURS INSPECTION CALL JASON JAWORSKY 520-909-5147 |
|
06/04/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* DO NOT OCCUPY AREAS UNTIL PARTIAL FINALS ARE APPROVED 1. PLEASE ADD 02010 TO PERMIT OK PVC CONDUIT FOR STARBUCKS |