Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T07CM00741
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/23/2007 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 05/21/2007 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. SECURE MC WITHIN 12" OF JUNCTION BOXES 2. MC RUN INSIDE METAL STUDS TO BE PROTECTED OR MOVED 3. EXCEEDING ALLOWED CONDUCTOR FILL ON SAME CUT IN BOXES. 4. EXCEEDING ALLOWED CONDUCTOR FILL ON SWITCH BOXES IN CONFERENCE ROOM. 5. INSTALL FOR SIDE SUPPORT ON DEVICE BOXES IN WALLS |
|
| 05/08/2007 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1. NOT READY FOR TEMP POWER SHEETROCK TO BE DONE & DEVICES INSTALLED 2. NEED TO POST BOND FOR TEMP POWER WHEN READY |
|
| 05/03/2007 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : There is no access to the site.| 920* DOORS LOCKED NO ACCESS |