Permit: T07CM00728

Parcel: 10824084A

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
05/29/2007 ELECTRIC - FINAL Approved
05/25/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
RECALL - LOCKED
05/21/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. DISHWASHER CORD TO BE PROPERLY INSTALLED
2. PANEL DIRECTORY NOT CORRECT
3. HAVE WRONG SIZE CLAMP ON WATER BOND
4. STILL NEED TO PROTECT SAT. DISH GROUND, STILL
HAVE L.V WIRING ON ROOF.
05/17/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. DATA PLATES STILL NOT IDENTIFIED ON AC'S -- NEC 440.4
2. PROVIDE PHYSICAL PROTECTION FOR SATELLITE GROUND ON ROOF -- NEC 250.120(C)
3. HAVE COIL OF LOW VOLTAGE WIRING ON ROOF?
4. PANEL DIRECTORY STILL NOT CORRECT -- NEC 408.4
5. INTERIOR METAL PIPING SYSTEMS TO BE BONDED TO SERVICE - NEC 250.104 (MISSED ON INTERMEDIATE)
05/14/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
PARTIAL INSPECTION
1. FINISH LOW VOLTAGE IN CEILING
2. PANEL DIRECTORY NOT CORRECTLY IDENTIFIED NEC 408
3. EMERGENCY LIGHTING NOT PER PLAN
4. IDENTIFY AC DISCONNECTS - NEC 110
5. MARK AC DISCONNECTS - NEC 440
6. PROPERLY GROUND SATELLITE DISH -- PER NEC 810.21