Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - ROUGH, SOIL
Permit Number - T07CM00726
Inspection Description - PLUMBING - ROUGH, SOIL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/10/2007 | PLUMBING - ROUGH, SOIL | Approved | IVRS - Inspection :* NEED TO SEE CLOSET FLANGES UNABLE TO LOCATE PERMIT OR INSPECTIONS HISTORY DID I GIVE YOU PERMISSION TO COVER THE WALLS? OK TO COVER UNDERGROUND OK TO COVER ALL AREAS |
|
04/09/2007 | PLUMBING - ROUGH, SOIL | Partial Approval | IVRS - Inspection :* 1) VERTICAL AND HORIZONTAL CHANGE OF DIRECTION TO BE A SWEEP |
|
04/04/2007 | PLUMBING - ROUGH, SOIL | Not ready for Inspection | IVRS - Inspection :* 1. NOT INSTALLED PER PLAN NO REDLINES ON SITE PLAN APPROVED DUMPING A DRAIN INTO A VENT 2003 UPC DOES NOT ALLOW THIS PLAN SHOWS 3" WASTE INSTALLED IS 4" IT WILL REQUIRE A FULL SIZE CLEANOUT 2. CLEANOUTS TO OPEN IN THE DIRECTION OF FLOW A TWO WAY CLEANOUT FITTING IS APPROVED WHERE THE BLDG. DRAIN MEETS THE BLDG SEWER ONLY. |
|
04/02/2007 | PLUMBING - ROUGH, SOIL | Not ready for Inspection | IVRS - Inspection :* 1. POST YOUR ADDRESS 2. DRAIN LINE MAY NOT DUMP INTO A VENT 3. REQUIRE FULL SIZE CLEANOUT AT 3" FLOOR SINK 4. REMOVE ROCKS AND DEBRIS FROM TRENCH 5. DOUBLE SANTEE NOT APPROVED FIXTURE DRAIN 6. FURNCO NOT APPROVED UNDER FLOOR. |