Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T07CM00726
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/03/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
05/02/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* REDO PANEL DIRECTORY SO IT IS NEAT, LEGIBLE AND CORRECT |
|
04/26/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. EMERGENCY LIGHT NOT WORKING 2. EMERGENCY LIGHTING TO BE FED BY LIGHTING CKT IN THAT AREA (NEC 700.12) 3. USE ANCHORS OR GO TO STUD FOR MC STRAPS 4. GRID SUPPORT WIRES NOT TO BE USED TO SUPPORT MC 5. PROPERLY IDENTIFY PANEL DIRECTORY |