Permit: T07CM00723

Parcel: 118200030


Addresses:

1211 S 11TH AV #01

Inspection Status: Approved

Inspection History: EXT METAL CLIPS/EXT SHEATHING

Date Description Inspector Results Comments
04/07/2008 EXT METAL CLIPS/EXT SHEATHING Approved IVRS - Inspection :*
03/06/2008 EXT METAL CLIPS/EXT SHEATHING Partial Approval IVRS - Inspection :*
1) COMPLY WITH DETAIL 2/4 A34
2) ALL JACK TRUSSES AT GIRDER TRUSS
3) OK TO WRAP
03/04/2008 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) MISSING HANGERS ON DBL GIRDER TRUSSES PER DETAIL 2 ON ROOF PLAN
2) NEED DBL 2 X STUDS UNDER DBL GIRDER IN UNIT #1
3) CHECK ALL CLIP AND NAILING
4) NEED DBL 2 X STUD ON END OF SHEARWALL-AT ENTRY UNIT #2
5) OK TO DRY IN ROOF
6) FRAMING WILL BE INSPECTED AT INTERMEDIATES