Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/05/2007 | MECHANICAL - ABOVE CEILING | Approved | FC4, 5 CONNECT CONDENSATE DRAIN CONDENSATE MISSING PLUG FC3 RELOCATE SPRINKLER OK FOR CEILING TILES LEAVE OUT AROUND FAN COILS |
|
| 08/29/2007 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* PROVIDE OVERFLOW SENSORS AS PER PLANS PROVIDE BUSHINGS IN FAN COIL CABINETS I.D EQUIPMENT RELOCATE LIGHT FROM BLOCKING ACCESS TO FAN COIL 1 STRAP ALL FLEX OFF OF GRID RELOCATE SUPPLY DIFFUSER FAN COIL 5 CHECK ALL FAN COILS |
|
| 07/26/2007 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) BATH CONDENSATES WRAPPED 2) OK TO SHEETROCK BATHROOM 3) LIDS FIRST FLOOR NORTH END |
|
| 07/18/2007 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* |