Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Date Description Inspector Results Comments
09/28/2007 PLUMBING - INTERMEDIATE Approved IVRS - Inspection :*
CLOSET FLANGES AND SHOWER LINER OK
09/13/2007 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
09/11/2007 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
LOCKED
08/31/2007 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
NEED TO SEE CLOSET FLANGES AND SHOWER PAN LINER
08/30/2007 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
BRAZE JOINT UNDER SLAB
INSTALL TRACER WIRE
SHADE W/CLEAN FILL
07/11/2007 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK TO COVER WALLS
NEED TO SEE CLOSET FLANGES SET AFTER FINISHED FLOOR
07/09/2007 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
- DWV TEST THRU ROOF OK
- DOMESTIC HW & CW OK
- ENERGY EFFICIENCY CODE REQUIRES 8' OF PIPE
INSULATION AT WH AND HEAT TRAPS.
- HORIZ ABS REQUIRES SUPPORT ALONG WEST WALL,
OK TO COVER OTHER AREAS
- SHWR PAN REQUIRES LINER INSPECTION
07/05/2007 PLUMBING - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. NOT UNDER TEST
2. CANNOT REDUCE TRAP ARM
3. CLEANOUTS SHALL BE TAKEN OFF ABOVE FLOW LINE
4. CLEANOUT EXTENSIONS SHALL BE MADE W/WYE PATTERN FITTINGS
5. HORIZ X HORIZ CHANGES OF DIRECTION REQUIRE SWEEPS OR 1/8" BENDS
6. SUPPORT HORIZONTAL RE-VENT PER T3-2