Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/28/2007 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection :* CLOSET FLANGES AND SHOWER LINER OK |
|
| 09/13/2007 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
| 09/11/2007 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* LOCKED |
|
| 08/31/2007 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* NEED TO SEE CLOSET FLANGES AND SHOWER PAN LINER |
|
| 08/30/2007 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* BRAZE JOINT UNDER SLAB INSTALL TRACER WIRE SHADE W/CLEAN FILL |
|
| 07/11/2007 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK TO COVER WALLS NEED TO SEE CLOSET FLANGES SET AFTER FINISHED FLOOR |
|
| 07/09/2007 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* - DWV TEST THRU ROOF OK - DOMESTIC HW & CW OK - ENERGY EFFICIENCY CODE REQUIRES 8' OF PIPE INSULATION AT WH AND HEAT TRAPS. - HORIZ ABS REQUIRES SUPPORT ALONG WEST WALL, OK TO COVER OTHER AREAS - SHWR PAN REQUIRES LINER INSPECTION |
|
| 07/05/2007 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. NOT UNDER TEST 2. CANNOT REDUCE TRAP ARM 3. CLEANOUTS SHALL BE TAKEN OFF ABOVE FLOW LINE 4. CLEANOUT EXTENSIONS SHALL BE MADE W/WYE PATTERN FITTINGS 5. HORIZ X HORIZ CHANGES OF DIRECTION REQUIRE SWEEPS OR 1/8" BENDS 6. SUPPORT HORIZONTAL RE-VENT PER T3-2 |