Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/23/2007 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
| 09/11/2007 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : A reinspection fee has been assessed for this inspection. Multiple inspection Locked-no access |
|
| 09/04/2007 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* OK TO TILE |
|
| 08/30/2007 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* FINISH PREVIOUS ITEMS 2 & 4 |
|
| 08/28/2007 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : Work is not complete enough to inspect.| 950* FINISH PREVIOUS ITEMS |
|
| 08/27/2007 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. IF MANUFACTURES CLIP ARE USED ON FIXTURES THEY MUST BE EFFECTIVE 2. SUPPORT VDV CABLING 725.6, 800.6 3. IF SCREWS ARE USED ON FIXTURES 4 ON CORNERS OR 2 ON CENTER 4. NO MORE THAN 360 DEG. IN A CONDUIT RUN 5. SUPPORT #4 GROUND WIRE & TERMINATE & SUPPORT 3/0 6. ELECTRICAL TO BE INDEPENDENTLY SUPPORTED 300.11 |
|
| 07/18/2007 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* OK BATHROOM HARD LIDS |