Permit: T07CM00718

Parcel: 141313370

Inspection Status: Approved

Inspection History: FRAMING

Permit Number - T07CM00718

Inspection Description - FRAMING

Inspection Status - Approved

Date Description Inspector Results Comments
05/09/2007 FRAMING Approved IVRS - Inspection :*
05/08/2007 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) SHIM 3 PT TRUSSES 2 TOTAL LAUNDRY ON FLOOR AND AT MASTER SHOWER 3 PT GIRDER
2) SHEAR TRANSFER, GARAGE TO DINING ROOM
3) REPAIR SHEAR AT MASTER BEDROOM MECH VENT BLK AND NAIL, PLEASE RED LINE PLAN FOR A 16 1/2" (STUD SPACE) INSIDE CLOSET FOR DUCT, SO STUDS WON'T NEED TO BE CUT
4) PEX 12" TO CAN FRONT ENTRY AND HALLWAY TO FRONT BEDROOM MASTER SHOWER
5) OVERSPAN STUD HALL BATH
6) WRONG SIZE NAILS IN HTT 16-16 D
7) NAIL OFF HIP HANGER EAST SIDE MARKED ON FLOOR
8) NO H20 IN DWV