Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
Permit Number - T07CM00718
Inspection Description - FRAMING
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/09/2007 | FRAMING | Approved | IVRS - Inspection :* | |
| 05/08/2007 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) SHIM 3 PT TRUSSES 2 TOTAL LAUNDRY ON FLOOR AND AT MASTER SHOWER 3 PT GIRDER 2) SHEAR TRANSFER, GARAGE TO DINING ROOM 3) REPAIR SHEAR AT MASTER BEDROOM MECH VENT BLK AND NAIL, PLEASE RED LINE PLAN FOR A 16 1/2" (STUD SPACE) INSIDE CLOSET FOR DUCT, SO STUDS WON'T NEED TO BE CUT 4) PEX 12" TO CAN FRONT ENTRY AND HALLWAY TO FRONT BEDROOM MASTER SHOWER 5) OVERSPAN STUD HALL BATH 6) WRONG SIZE NAILS IN HTT 16-16 D 7) NAIL OFF HIP HANGER EAST SIDE MARKED ON FLOOR 8) NO H20 IN DWV |