Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T07CM00717
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/29/2007 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* AIR BALANCE OK CORRECTIONS HAVE BEEN MADE OK FOR FINAL |
|
11/27/2007 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* 1) REMOVE SHIMS FROM UNDER SLEEPERS AND RELOCATE UNDER CONDENSORS 2) PROVIDE A ROOF JACK AT ELECTRIC PENETRATION FOR EVAP COOLER 3) PERMANENTLY I.D. ALL EQUIPMENT 4) PROVIDE COIL GUARDS 5) CHECKED FIRE WRAP 6) OK FOR CEILING TILES |