Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T07CM00717
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/30/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
11/29/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* NEED TO COMPLETE NOTE #7 LAST INSP. OK FOR TCO |
|
11/27/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) EM LIGHTING NOT WORKING/MISSING EM LIGHT 2) KITCHEN RECEPTACLES TO BE GFI PROTECTED 3) BATHROOM RECEPTACLES TO BE GFI PROTECTED-NEED EXTENSIONS 4) MISSING BLOCKS AND K.O.'S AND PLATES ON DEVICES 5) SEAL PENETRATIONS INTO COOLERS 6) NEED DETAILED PANEL SCHEDULES 7) DISHWASHER TO BE WIRED. DISCONNECT NEEDS WORKING CLEARANCES OR LOCKING DEVICE ON BREAKER 8) FIX OPEN WIRING TO EXHAUST FAN |