Permit: T07CM00717

Parcel: 14117007Q

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T07CM00717

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
11/30/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
11/29/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
NEED TO COMPLETE NOTE #7 LAST INSP.
OK FOR TCO
11/27/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) EM LIGHTING NOT WORKING/MISSING EM LIGHT
2) KITCHEN RECEPTACLES TO BE GFI PROTECTED
3) BATHROOM RECEPTACLES TO BE GFI PROTECTED-NEED EXTENSIONS
4) MISSING BLOCKS AND K.O.'S AND PLATES ON DEVICES
5) SEAL PENETRATIONS INTO COOLERS
6) NEED DETAILED PANEL SCHEDULES
7) DISHWASHER TO BE WIRED. DISCONNECT NEEDS WORKING CLEARANCES OR LOCKING DEVICE ON BREAKER
8) FIX OPEN WIRING TO EXHAUST FAN