Permit: T07CM00716

Parcel: 11522002A


Addresses:

1400 W SPEEDWAY BL

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
11/21/2008 MECHANICAL - FINAL Approved IVRS - Inspection :*
11/20/2008 MECHANICAL - FINAL Cancelled IVRS - RI canceled
11/20/2008 MECHANICAL - FINAL Not ready for Inspection IVRS - Inspection :*
11/18/2008 MECHANICAL - FINAL Not ready for Inspection IVRS - Inspection :*
1. PROVIDE D.S DAMPER TEST
2. CHANGE OUT NON-RATED WOOD ON ROOF
3. PROVIDE SUN SHIELD AT EC-1 FLEX
4. IDENTIFY HEAT STRIP DATA PLATE
10/07/2008 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
1. PROVIDE DUCT SMOKE DETECTORS ON SMOKE DAMPERS AS REQUIRED BY CODE AND/OR SPECS.
2. SEAL DUCTING AT FIRE/SMOKE DAMPERS
3. OK FOR TILES MECHANICAL ONLY
09/30/2008 MECHANICAL - FINAL Not ready for Inspection IVRS - Inspection :*