Permit: T07CM00716

Parcel: 11522002A


Addresses:

1400 W SPEEDWAY BL


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T07CM00716

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
11/20/2008 ELECTRIC - FINAL Approved IVRS - Inspection :*
11/18/2008 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :
CANCELED
11/03/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. PANEL DIRECTORIES TO BE AS PER 408.4 DISTINGUISHABLE FROM ONE ANOTHER AND LEGIBLE -- NO ABBREVIATIONS
2. BOXES MORE THAN 1/4" - 314.20
3. PLEASE VERIFY DIMMER LOADS AND DERATING FOR
MULTI-GANG BOXES
4. HALL EM LIGHTS NOT WORKING
5. BOND DISCONNECT - W/H

ROOF:
1. LABEL DISCONNECTS
2. TIGHTEN LOOSE FITTINGS
3. BOND DISCONNECTS