Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/20/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 11/18/2008 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection : CANCELED |
|
| 11/03/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. PANEL DIRECTORIES TO BE AS PER 408.4 DISTINGUISHABLE FROM ONE ANOTHER AND LEGIBLE -- NO ABBREVIATIONS 2. BOXES MORE THAN 1/4" - 314.20 3. PLEASE VERIFY DIMMER LOADS AND DERATING FOR MULTI-GANG BOXES 4. HALL EM LIGHTS NOT WORKING 5. BOND DISCONNECT - W/H ROOF: 1. LABEL DISCONNECTS 2. TIGHTEN LOOSE FITTINGS 3. BOND DISCONNECTS |