Permit: T07CM00711

Parcel: 10511061R

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T07CM00711

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
07/09/2007 ELECTRIC - FINAL Approved
06/28/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
OK TEMP C OF O
1. CALL FOR FINAL WHEN REMAINDER OF EMERGENCY LIGHTING INSTALLED STILL NEED TO CHECK X-FORMER GEC
06/26/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. PANEL DIRECTORIES TO BE LABELED AS PER 408.4
NO ABBREVIATIONS - MISSING ONE DIRECTORY "MP"
2. WHICH CIRCUIT CONTROLS LIGHTS IN BACK AREAS
3. ATTACH ALL AUXILIARY CONTACTORS -- BOX OVERFILLED
PROPERLY GROUND BOX
4. CANNOT CHECK EM & EXIT LIGHTING DUE TO CIRCUIT LABELING.
5. JUNCTION BOXES TO BE SUPPORTED BY OTHER MEANS THAN CONDUIT
6. GROUND LIGHT FIXTURES
7. SEAT FITTINGS INTO FIXTURES
8. FILL UNUSED OPENINGS IN JUNCTION BOXES

NOT FINISHED INSPECTING
06/25/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. HAVE MISWIRED RECEPTACLES - PLUG CHECK ALL
2. HAVE OPEN J-BOX
3. CHECK EMERGENCY LIGHTING
4. SEAL UNUSED OPENING PANEL MP
5. PROVIDE GROUNDING ELECTRODE FOR TRANSFORMER
6. CHECK PANEL DIRECTORY'S

PARTIAL INSPECTION
06/21/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
DO NOT CALL BEFORE JOB IS COMPLETE AND READY FOR FINAL INSPECTION OR A FEE MAY BE CHARGED