Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T07CM00711
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/09/2007 | ELECTRIC - FINAL | Approved | ||
06/28/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* OK TEMP C OF O 1. CALL FOR FINAL WHEN REMAINDER OF EMERGENCY LIGHTING INSTALLED STILL NEED TO CHECK X-FORMER GEC |
|
06/26/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. PANEL DIRECTORIES TO BE LABELED AS PER 408.4 NO ABBREVIATIONS - MISSING ONE DIRECTORY "MP" 2. WHICH CIRCUIT CONTROLS LIGHTS IN BACK AREAS 3. ATTACH ALL AUXILIARY CONTACTORS -- BOX OVERFILLED PROPERLY GROUND BOX 4. CANNOT CHECK EM & EXIT LIGHTING DUE TO CIRCUIT LABELING. 5. JUNCTION BOXES TO BE SUPPORTED BY OTHER MEANS THAN CONDUIT 6. GROUND LIGHT FIXTURES 7. SEAT FITTINGS INTO FIXTURES 8. FILL UNUSED OPENINGS IN JUNCTION BOXES NOT FINISHED INSPECTING |
|
06/25/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. HAVE MISWIRED RECEPTACLES - PLUG CHECK ALL 2. HAVE OPEN J-BOX 3. CHECK EMERGENCY LIGHTING 4. SEAL UNUSED OPENING PANEL MP 5. PROVIDE GROUNDING ELECTRODE FOR TRANSFORMER 6. CHECK PANEL DIRECTORY'S PARTIAL INSPECTION |
|
06/21/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* DO NOT CALL BEFORE JOB IS COMPLETE AND READY FOR FINAL INSPECTION OR A FEE MAY BE CHARGED |