Permit: T07CM00711

Parcel: 10511061R

Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Permit Number - T07CM00711

Inspection Description - ELECTRIC - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
07/09/2007 ELECTRIC - ABOVE CEILING Approved
06/01/2007 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
OK SHOWROOM AREA
05/30/2007 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. SUPPORT CONDUITS AS PER 358.30 PER VDV CABELING
2. PLEASE VERIFY RATING OF STUD TO SUPPORT WEIGHT FOR WALKWAY ACCESS
3. FINISH PREVIOUS ITEMS 2, 3, 4
05/25/2007 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. SUPPORT M/C CABLES WITHIN 12" OF CANS AND STUBS
2. PROPERLY SUPPORT FLEX CONDUIT
3. PROPERLY SUPPORT VDV CABELING 725.6 & 800.6
4. JUNCTION BOXES TO BE ACCESSIBLE