Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/09/2007 | ELECTRIC - ABOVE CEILING | Approved | ||
06/01/2007 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* OK SHOWROOM AREA |
|
05/30/2007 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. SUPPORT CONDUITS AS PER 358.30 PER VDV CABELING 2. PLEASE VERIFY RATING OF STUD TO SUPPORT WEIGHT FOR WALKWAY ACCESS 3. FINISH PREVIOUS ITEMS 2, 3, 4 |
|
05/25/2007 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. SUPPORT M/C CABLES WITHIN 12" OF CANS AND STUBS 2. PROPERLY SUPPORT FLEX CONDUIT 3. PROPERLY SUPPORT VDV CABELING 725.6 & 800.6 4. JUNCTION BOXES TO BE ACCESSIBLE |