Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/06/2007 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 10/12/2007 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK TO COVER WALLS RECALL FOR ABV CEILING INSULATION AND HANGERS RECALL FOR CLOSET FLANGE INSP |
|
| 10/02/2007 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* AT LAVS: TRAP AND TRAP ARM SHALL BE THE SAME SIZE - DOMESTIC WATER PIPING NOT SIZED PER PLAN AT WC'S - NOT PER SPEC BOOK - BRAZED JOINTS REQUIRED ON 2 1/2" - ISOLATION VALVES ARE SHOWN UPSTREAM OF LAVITORY CONN - OVERSIZED HANGERS NEEDED TO PROVIDE CONTINUOUS INSULATION THROUGH SUPPORTS ON HW - 2.08 #5 TRISOLATOR #500 REQUIRED ON CW - ALSO, 1/2" ROD ON 2 1/2" - COPPER PIPING HAS NOT BEEN DEBURRED - INSTALL PIPING TO THE MIN. STANDARDS REQUIRED BY CODE AND PER JOB SPECIFICATIONS ALSO, SUPPORT BRANCHES. |