Permit: T07CM00702

Parcel: 133220010


Addresses:

502 N CARIBE AV

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
11/30/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
11/27/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) ROOF: MAINTAIN WORKING CLEARANCES 110.26
2) ISOLATE AND PROTECT CONDUCTORS TO RELAY
3) INSTALL RELAY IN AN ENCLOSURER
4) GFI COVERS TO OPEN
5) PROTECT SEAL TITE FROM SHARP METAL EDGES
6) PLEASE PROVIDE INTER LOCK RELAY DIAGRAM
11/21/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1. INSTALL OUTSIDE LIGHTING
2. BOXES MORE THAN 1/4" 314.20
3. FILL UNUSED PORTION OF COVER PLATES
4. FINISH OCCUPANCY SENSORS
5. FINISH ELECTRIC ROOM