Permit: T07CM00699

Parcel: 205661300

Inspection Status: Approved

Inspection History: FRAMING

Date Description Inspector Results Comments
11/01/2007 FRAMING Approved IVRS - Inspection :*
10/29/2007 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) PROVIDE BLOCKING AT TOP OF SHEAR WALLS FOR NAILING SHEAR
2) SHEAR MUST EXTEND FROM BOTTOM PLATE TO TOP PLATE
3) ANCHOR SHEARWALL BY GARAGE
4) ANCHOR INTERIOR BEARING WALL WITH WEDGE ANCHORS AT 6" ON CENTER WITH 22" EMEDMENT
5) BLOCK SHEARWALL 4" ON CENTER
6) FIREBLOCK DROP CEILING IN STORAGE
7) FIREPLACE HEARTH MUST EXTEND 16" SEE PAGE 26 OF ?
8) TRIPPLE 2 X POSTS REQUIRED UNDER TRIPPLE LAM BEAM ENTRY
9) FURNACE WEST "B"-1" TO COMBUSTIBLE
10) DRY WALL BLOCK WEST TAB
11) VENT GAS SLEVE OUTSIDE
12) FIRE STOP DINING ROOM POP OUT WALL
13) ISOLATE COPPER FROM GAS LINE AND FIRE STOP CHASE-LAUNDRY
14) NOTE: DO NOT PUT ELECTRIC OUTLETS UNDER OVERHANGS GREATER THAN 6"