Permit: T07CM00690

Parcel: 13316030E

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
04/26/2007 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
04/19/2007 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
LOCKED NO ACCESS
04/06/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) SUPPRT FLEX CONDUIT UP OFF PIPES
2) PLEASE PROVIDE BACK SUPPORT FOR BOXES IN ROOM 103
3) ARE BOXES LISTED FOR BONDING PER 250.97-ALSO FITTINGS
4) VDV CABELING TO BE PER 725.3 AND 6 & 800.3 AND 6
5) OK LIGHTING
6) BOXES MORE THAN 1/4" FROM BOX TO SURFACE NEED APPRIOVED EXTENDER RINGS PER 314.20
03/14/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK WALLS
*VDV CABLING ABOVE CEILING TO BE AS PER 725.3 & 6
800.3 & 6