Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T07CM00690
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/26/2007 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
04/19/2007 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* LOCKED NO ACCESS |
|
04/06/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) SUPPRT FLEX CONDUIT UP OFF PIPES 2) PLEASE PROVIDE BACK SUPPORT FOR BOXES IN ROOM 103 3) ARE BOXES LISTED FOR BONDING PER 250.97-ALSO FITTINGS 4) VDV CABELING TO BE PER 725.3 AND 6 & 800.3 AND 6 5) OK LIGHTING 6) BOXES MORE THAN 1/4" FROM BOX TO SURFACE NEED APPRIOVED EXTENDER RINGS PER 314.20 |
|
03/14/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK WALLS *VDV CABLING ABOVE CEILING TO BE AS PER 725.3 & 6 800.3 & 6 |