Permit: T07CM00689

Parcel: 128100540

Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Date Description Inspector Results Comments
03/13/2007 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection :*
03/12/2007 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. SECURE/SUPPORT MC CABLE WITHIN 12" OF BOXES/DISCONNECTS.
2. SECURE/SUPPORT METAL FLEX WITHIN 12" OF BOXES/DISCONNECTS
3. SUPPORT ALL JUNCTION BOXES PER CODE
4. SUPPORT EMT PER CODE
03/09/2007 ELECTRIC - ABOVE CEILING Cancelled IVRS - RI canceled