Permit: T07CM00688

Parcel: 11307111B


Addresses:

1722 E HEDRICK DR

Inspection Status: Approved

Inspection History: FRAMING

Date Description Inspector Results Comments
04/07/2008 FRAMING Approved IVRS - Inspection :*
04/04/2008 FRAMING Partial Approval IVRS - Inspection :*
04/03/2008 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
04/02/2008 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
02/26/2008 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) ELECTRICAL PLANS NOT CORRECT (NO 600 AMP SERVICE APPROVED)
2) NEED APPROVED TRUSS CALCS ON SITE FOR REVIEW AS CALLED OUT
3) NEED A COMPLETE SET OF APPROVED PLANS ON SITE
4) SUB-PANELS MUST BE MADE UP COMPLETELY TO RELEASE POWER WITH TEMP SERVICE GFCI OUTLETS
5) NO WATER TEST ON GARAGE ABS
6) BOND GAS LINE
7) PROTECT ALL WORK WITH NAIL PLATES
8) FOLLOW ALL APPROVED FRAMING DETAILS PER PLANS
9) INSPECTION STOPPED