Permit: T07CM00679

Parcel: 10511061R

Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Date Description Inspector Results Comments
07/25/2007 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection :*
07/24/2007 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
There is no access to the site.| 920*
DOOR LOCKED
07/19/2007 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
See detailed listing on site.| 999*
PARTIAL CEILING INSPECTION
1. TRACK LIGHTING TO HAVE SUPPORT WIRES CONNECTED TO THE TRACK AT ENDS AND 4' INTERVALS
2. SECURE EQUIPMENT INTO STUDS OR ANCHORS - NOT JUST DRYWALL
3. MC TO BE SECURED WITHIN 12" OF TERMINATIONS
4. GROUND ALL METAL BOXES
5. CLOSE UP OPEN J-BOXES REMOVE UNUSED EQUIPMENT
FINISH L.V WIRING
6. EMT TO BE SQUARE INTO J-BOXES STRAPPED WITH 36" OF ENCLOSURES
06/14/2007 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*