Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T07CM00679
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/25/2007 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
07/24/2007 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : There is no access to the site.| 920* DOOR LOCKED |
|
07/19/2007 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* PARTIAL CEILING INSPECTION 1. TRACK LIGHTING TO HAVE SUPPORT WIRES CONNECTED TO THE TRACK AT ENDS AND 4' INTERVALS 2. SECURE EQUIPMENT INTO STUDS OR ANCHORS - NOT JUST DRYWALL 3. MC TO BE SECURED WITHIN 12" OF TERMINATIONS 4. GROUND ALL METAL BOXES 5. CLOSE UP OPEN J-BOXES REMOVE UNUSED EQUIPMENT FINISH L.V WIRING 6. EMT TO BE SQUARE INTO J-BOXES STRAPPED WITH 36" OF ENCLOSURES |
|
06/14/2007 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* |