Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - UNDERGROUND
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/01/2007 | ELECTRIC - UNDERGROUND | Approved | IVRS - Inspection :* | |
| 06/14/2007 | ELECTRIC - UNDERGROUND | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) SHEET METAL SCREWS NOT ALLOWED FOR GROUNDING 2) CONDUCTOR TO BE IDENTIFIED AS PER 200.6 AND 200.7 3) SUPPORT CONDUIT AS PER CODE 358.30 4) BOX SUPPORTS TO BE AS PER 312.23 5) ONLY ONE CONDUCTOR PER LUG 110.3 (B) 6) CORRECTLY IDENTIFY GROUNDING CONDUCTOR 7) USE APPROVED CONDUIT FITTINGS 8) CEILING WORK TO BE AS PER 300.11 9) PLEASE VERIFY QUALIFIED ELECTRICAL PERSON |