Inspection History Details
Inspection Status: Approved
Inspection History: REINFORCED MASONRY PRE-GROUT
Permit Number - T07CM00676
Inspection Description - REINFORCED MASONRY PRE-GROUT
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/11/2007 | REINFORCED MASONRY PRE-GROUT | Approved | IVRS - Inspection :* 1) APPROVED AT 7'-4" CMU WALL TO TOP OUT |
|
05/10/2007 | REINFORCED MASONRY PRE-GROUT | Not ready for Inspection | IVRS - Inspection :* | |
05/03/2007 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* NOTE: 48" A.F.F.E, 8X8X16 WITH #4 VERT. @ 16" O.C AND HORIZ. JOINT REINF. AT 16" O.C |
|
04/26/2007 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* 24" A.F.F.E 2 COURSES OF CMU WALL, PRIOR TO GROUT PROVIDE CONTINUATION OF VERTICAL REINFORCING AND COMPLIANCE WITH THE MINIMUM OVERLAP IN ACCORDANCE WITH MSCJ AND DETAIL 9 ON SHEET S1.1 OR COMPLETE CMU TO TOPOUT AND CALL FOR REINFORCING MASONRY PRE-GROUT INSPECTION PRIOR TO GROUT. |