Permit: T07CM00650

Parcel: 140430130

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Permit Number - T07CM00650

Inspection Description - MECHANICAL - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
06/11/2009 MECHANICAL - FINAL Approved IVRS - Inspection :*
MECH. ENGINEER STAMPED RFI AND SPOKE WITH JIM M.
06/10/2009 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
NEEDS LETTER ACCEPTING BALANCE REPORT FROM ENGINEER
06/01/2009 MECHANICAL - FINAL Not ready for Inspection IVRS - Inspection :*
04/13/2009 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
PROVIDE AMENDED BALANCE REPORT FOR TU-4
ITEMS DATED 12/4/08 OK
04/09/2009 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
12/04/2008 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
1. ALL LIFE SAFETY ISSUES OBSERVED SEE BUILDING INSPECTOR FOR TEMP C OF O
2. PROVIDE FLEX CONNECTORS ON GAS PIPING PER (11) PL501
3. ISOLATE COPPER "T's" ON ROOF
4. PROVIDE GAS PIPING SUPPORT ON WATER HEATER
5. PROVIDE VENT PIPING INSTALLATION INSTRUCTIONS ON WATER HEATER 90%
6. PROVIDE AIR BALANCE REPORT
7. DUCT SMOKE DETECTOR TEST OK X5
12/03/2008 MECHANICAL - FINAL Not ready for Inspection IVRS - Inspection :*
AHU-2 OK
ON DUCT SMOKE DETECTOR TEST, NEED TO PROVIDE APPROVED ACCESS
AHU-1 OK