Inspection History Details
Inspection Status: Approved
Inspection History: SITE - SEWER
Permit Number - T07CM00650
Inspection Description - SITE - SEWER
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/26/2008 | SITE - SEWER | Approved | IVRS - Inspection :* | |
12/20/2007 | SITE - SEWER | Partial Approval | IVRS - Inspection :* 1. PROVIDE VERIFICATION OF GRADE 2. BENCH IN MANHOLE OK |
|
10/02/2007 | SITE - SEWER | Partial Approval | IVRS - Inspection :* AIR TEST FROM MANHOLE TO STUBS 5' FROM BUILDINGS OK |
|
09/28/2007 | SITE - SEWER | Partial Approval | IVRS - Inspection :* 6" SDR 35 CONTINUOUS TO MAINTENANCE BLD 5' AND 4" SDR 35 CONTINUES TO WAREHOUSE BLD 5' AIR TEST & VERIFICATION OF GRADE AT LATER DATE |
|
09/27/2007 | SITE - SEWER | Not ready for Inspection | IVRS - Inspection :* CONTRACTOR CANCELLED |
|
09/26/2007 | SITE - SEWER | Partial Approval | IVRS - Inspection :* PIPING TO CLEANOUT LOCATION ON EAST SIDE OF STREET OK |
|
09/25/2007 | SITE - SEWER | Partial Approval | IVRS - Inspection :* 6" SDR 35 FROM EXISTING MANHOLE (1) CLEANOUT INSTALLED APP. 40 FROM MANHOLE, PIPING APP. 80' GOING EAST, BEDDING, LAYING, SHADING, TRACER WIRE. SHALL PROVIDE LETTER GIVING OK FOR SDR 35 IN PLACE OF PVC SCH 40 STAMPED BY ENGINEER, AIR TESTING & VERIFICATION OF GRADE BY ENGINEER OR LICENSED SURVEYOR AT LATER DATE |