Permit: T07CM00647

Parcel: 10511061R

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T07CM00647

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
04/09/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
04/06/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) INSTA HOT NOT CONNECTED
2) NO ONE PRESENT TO PROVIDE ACCESS AS PER PREVIOUS INSPECTION
04/04/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. INSTA-HOT NOT WIRED -- 2.4 KW TO BIG FOR 20 AMP CKT?
2. PROVIDE ACCESS TO BRANCH CKT PANEL FOR THIS SPACE

OK TO OCCUPY THIS SPACE