Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T07CM00647
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/09/2007 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
03/28/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK TO COVER WALLS AND CEILING |
|
03/26/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) FINISH PROTECTION AND SUPPORTING OF M/C CABLES TO SWITCHES BY DOOR |
|
03/22/2007 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. PROVIDE NAIL PLATES FOR MC WHERE REQUIRED NEC 330.17 2. PROVIDE BACK SUPPORT FOR RECEPTACLE BOX - NEC 314.23 3. BRING J-BOX FLUSH TO WALL - NEC 314.20 4. SECURE MC INTO SWITCH BOX -- NEC 330.30 |