Inspection History Details
Inspection Status: Cancelled
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T07CM00642
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Cancelled
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/06/2007 | ELECTRIC - INTERMEDIATE | Cancelled | IVRS - RI canceled | |
06/05/2007 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
06/04/2007 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* ATTACH FIXTURE TO GRID AND 2 SUPPORT WIRES ON OPPOSITE CORNERS. OK RECEPTACLES X-RAY COUNTER |
|
05/30/2007 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* OK TO USE FRONT DESK OK FIRE ALARM CONDUIT ROOM X-RAY WAITING 1. BOXES MORE THAN 1/4" FROM BOX TO SURFACE NEED APPROVED EXTENDER RINGS 314.20 |
|
04/30/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. OK ELECTRIC ROUGH FOR FRONT DESK 2. OK WALLS X-RAY AREA NEED TO CONNECT GROUND WIRE TO BOXES 3. OK RECEPTION DESK CEILING FOR CAMERAS |
|
03/20/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. CHECK 2 HORN STROKES RELOCATED OUT OF NEW SHEETROCK SOFFIT. 2. CHECK 3 JUNCTION BOXES RELOCATED OUT OF NEW SHEETROCK SOFFIT. 3. OK TO SHEETROCK SOFFIT 4. OK TO COVER COLUMN |
|
03/15/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK UNDERGROUND PVC & RIDGID 90 DEG'S. WALL TO DESK TO WALL OK PONY WALLS |